Reference IEC-101 Slave ProLinx Communication Gateway
Protocol Manual IEC 60870-5-101 v3 Slave (Firmware version 3.xx)
Page 90 of 159 ProSoft Technology, Inc.
August 6, 2010
Select/Operate Timeout Parameter
Use the Select/Operate Timeout parameter to configure the select/operate
timeout period. After the gateway receives the Select command, it will wait for
this period of time to receive the Execute command for the same point address. If
the gateway does not receive an Execute command within this period of time, it
will require another Select operation before the Execute operation will be
accepted and acted upon.