IEC-101 Slave ProLinx Communication Gateway Reference
IEC 60870-5-101 v3 Slave (Firmware version 3.xx) Protocol Manual
ProSoft Technology, Inc. Page 83 of 159
August 6, 2010
M_SP_NA
A Monitor Single-Point information object occupies one binary bit and uses bit
addressing. For example, if you configured the following points as shown:
The following table describes how these points would be stored in the gateway:
Inf. Object Address Module Database Address
100 Bit 0 of word 100 (Bit address 1600)
101 Bit 1 of word 100 (Bit address 1601)
102 Bit 2 of word 100 (Bit address 1602)