IEC-101 Slave ProLinx Communication Gateway Reference
IEC 60870-5-101 v3 Slave (Firmware version 3.xx) Protocol Manual
ProSoft Technology, Inc. Page 105 of 159
August 6, 2010
Data Type Level
You can configure whether a data type should generate events. Each data type
has a configuration parameter to control the generation of events:
In the example above, only the M_SP_NA points would generate events.
Point Level
You can configure whether each point should generate events using the Group
field for each point configuration. To disable event generation for a specific port,
set the value to 40000000.