IEC-101 Slave ProLinx Communication Gateway Reference
IEC 60870-5-101 v3 Slave (Firmware version 3.xx) Protocol Manual
ProSoft Technology, Inc. Page 89 of 159
August 6, 2010
Example (C_SC_NA)
In the example above, each time the gateway receives a value of one (1) in
Control Single Command 700, it will send a response by placing a value of one
(1) in Monitor Single-Point # 100 at database bit address 1600.
Some of the Command points may be configured to require a Select command
before they will act on an Execute command.