PLX8x-MNET-61850 ♦ Communication Gateway ProSoft 61850 Configuration Manager
Modbus TCP/IP to IEC 61850 User Manual
ProSoft Technology, Inc. Page 51 of 228
May 14, 2014
PLC Map View
Right-click on the Quantum, Premium, or M340 icon and choose PLC MAP VIEW.
The Map View window gives you information about all of the tags mapped to this
PLC. The fields are:
Direction
PLC Start MB Address
PLX Start MB Address
Tag Name
Size
From this window, you can EXPORT THE PROCESSOR FILES or PRINT this list.
DIRECTION: This shows "MNET" with an arrow. It indicates in which direction the
data will move.
"MNET →", indicates the data is moving from the gateway’s MNET Client to a
remote Modbus TCP/IP server device (usually a Modicon PLC or PAC). This
is IEC 61850 data being read from the IED and pushed from the gateway to
the Modbus device.
"MNET ←" indicates the data is moving from a remote Modbus TCP/IP Client
device to the gateway’s MNET server. This is mapped to IEC 61850 writable
data. The Modbus device (usually a Modicon PLC or PAC) writes the data to
the gateway, and the gateway writes it to the IED.
PLC START MB ADDRESS: This is the PLC address in the PLC that this data will
reside. This is derived, and based upon the address configured in the "Modbus
TCP/IP Device Configuration" window, PLC Read Start Register (%MW) or PLC
Write Start Register (%MW) field. In Unity Pro addressing, "%MW1" means the
same as Modbus 40,001 or 400,001 in common Modbus addressing.