Diagnostics and Troubleshooting PLX8x-MNET-61850 Communication Gateway
User Manual Modbus TCP/IP to IEC 61850
Page 120 of 228 ProSoft Technology, Inc.
May 14, 2014
Modbus Communication Error Codes
Code
Description
-1
CTS modem control line not set before transmit
-2
Timeout while transmitting message
-11
Timeout waiting for response after request
253
Incorrect slave address in response
254
Incorrect function code in response
255
Invalid CRC/LRC value in response
MNET Client Specific Errors
Code
Description
-33
Failed to connect to server specified in command
-36
MNET command response timeout
-37
TCP/IP connection ended before session finished
Command List Entry Errors
Code
Description
-40
Too few parameters
-41
Invalid enable code
-42
Internal address > maximum address
-43
Invalid node address (<0 or >255)
-44
Count parameter set to 0
-45
Invalid function code
-46
Invalid swap code
-47
ARP could not resolve MAC from IP (bad IP address, not part of a
network, invalid parameter to ARP routine).
-48
Error during ARP operation: the response to the ARP request did
not arrive to the gateway after a user-adjustable ARP Timeout.
Last Error
Execution Count: Total number of times this command was sent / triggered.