Reference PLX8x-MNET-61850 Communication Gateway
User Manual Modbus TCP/IP to IEC 61850
Page 164 of 228 ProSoft Technology, Inc.
May 14, 2014
Quality
Quality is packed as 13 bits.
(This table has been taken directly from the IEC 61850 Standard document)
Functional Constraints
Each IEC 61850 Data Attribute has a Functional Constraint (FC), which shows
what the data is or how it is used. For example, Data Attributes with FC=ST are
status data. Data Attributes with FC=CO can be controlled.
The Data Attributes Functional Constraints can be seen in the IEC Mapping Tool
window, for example:
Note: the little icons provide information. DO is for Data Object. Within the DO,
there may be multiple levels of data. When we get down to the Data Attribute
level, the functional constraint of the Data Attribute is shown in the icon, e.g. CO
for Control, ST for Status Information, and CF for Configuration.