PLX8x-MNET-61850 ♦ Communication Gateway Diagnostics and Troubleshooting
Modbus TCP/IP to IEC 61850 User Manual
ProSoft Technology, Inc. Page 103 of 228
May 14, 2014
5.3 Driver Status Data
These are the status registers:
Driver Status Register’s possible values are:
1 = Ok
0 = Failed or Driver startup/restart is occurring
61850 IED status registers:
Possible values are:
1 - Node connected
0 - Node initializing
-1 - Node disconnected. It may take up to 15 minutes to show this, and will first
show as “-2”.
-2 – Node in error
5.3.1 Rebooting the Gateway
If you need to reboot the ProSoft gateway, there are a few ways to do it:
Disconnect and reconnect power from the gateway.
From the PLC or generic Modbus device, write to the gateway’s address
65535 and it will reboot
From the webpage on the ProSoft gateway, use the Reboot Gateway feature