2.1.2 Create the Module
1 Right-click
I/O
C
ONFIGURATION
and choose N
EW
M
ODULE
2 Select 1769-MODULE
3 Set the Module Properties values as follows:
Parameter Value
Name Enter a module identification string. Example: MVI69MCM
Description Enter a description for the module. Example: ProSoft
communication module for Serial Modbus communications.
Comm Format Select Data-INT
Slot Enter the slot number in the rack where the MV69-MCM
module will be installed.
Input Assembly Instance 101
Input Size 62 / 122 / 242
Output Assembly Instance 100
Output Size 61 / 121 / 241
Configuration Assembly Instance 102
Configuration Size 0