Prosoft-technology MVI69-MCM Manuel d'utilisateur Page 153

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 167
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 152
MVI69-MCM ♦ CompactLogix or MicroLogix Platform Reference
Modbus Communication Module User Manual
ProSoft Technology, Inc. Page 153 of 167
March 22, 2011
Offset Content Description
6695 Parse Block
Count
This field contains the total number of blocks successfully parsed
that were received from the processor.
6696 Command Event
Block Count
This field contains the total number of command event blocks
received from the processor.
6697 Command Block
Count
This field contains the total number of command blocks received
from the processor.
6698 Error Block
Count
This field contains the total number of block errors recognized by
the module.
6699 Port 1 Current
Error
For a slave port, this field contains the value of the current error
code returned. For a Master port, this field contains the index of the
currently executing command.
6700 Port 1 Last Error For a slave port, this field contains the value of the last error code
returned. For a Master port, this field contains the index of the
command with an error.
6701 Port 2 Current
Error
For a slave port, this field contains the value of the current error
code returned. For a Master port, this field contains the index of the
currently executing command.
6702 Port 2 Last Error For a slave port, this field contains the value of the last error code
returned. For a Master port, this field contains the index of the
command with an error.