Contents MVI56E-DNPNET ♦ ControlLogix Platform
User Manual DNPNET Ethernet Client/Server Communication Module
Page 32 of 140 ProSoft Technology, Inc.
February 13, 2015
DNPNET.CONFIG.DNP3_Ser
ver.Analog16_Input_Class
This parameter specifies the default class to
be utilized for all the 16-bit analog input points
in the DNP database that are not defined in
the override list section.
DNPNET.CONFIG.DNP3_Ser
ver.Analog32_Input_Class
This parameter specifies the default class to
be utilized for all the 32-bit analog input points
in the DNP database that are not defined in
the override list section.
DNPNET.CONFIG.DNP3_Ser
ver.Float_Class
This parameter specifies the default class to
be utilized for all the float input points in the
DNP database that are not defined in the
override list section.
DNPNET.CONFIG.DNP3_Ser
ver.Double_Class
This parameter specifies the default class to
be utilized for all the double input points in the
DNP database that are not defined in the
override list section.
DNPNET.CONFIG.DNP3_Ser
ver.Analog16_Input_Deadban
d
This parameter specifies the default deadband
value assigned to all points not defined in the
override list for the 16-bit analog input point
type in the DNP database.
DNPNET.CONFIG.DNP3_Ser
ver.Analog32_Input_Deadban
d
This parameter specifies the default deadband
value assigned to all points not defined in the
override list for the 32-bit analog input point
type in the DNP database.
DNPNET.CONFIG.DNP3_Ser
ver.Float_Deadband
This parameter specifies the default deadband
value assigned to all points not defined in the
override list for the float input point type in the
DNP database.
DNPNET.CONFIG.DNP3_Ser
ver.Double_Deadband
0 to maximum
double value
This parameter specifies the default deadband
value assigned to all points not defined in the
override list for the double input point type in
the DNP database.
DNPNET.CONFIG.DNP3_Ser
ver.SelectOperate_Arm_Time
Time period after select command received in
which operate command will be performed.
After the select command is received, the
operate command will only be honored if it
arrives within this period of time.
DNPNET.CONFIG.DNP3_Ser
ver.Write_Time_Interval
Time interval to set the need time IIN bit
(0=never), which will cause the client to write
the time. Stored in milliseconds in the module
memory.
DNPNET.CONFIG.DNP3_Ser
ver.Spare1_Always_0
IED can request acknowledgement from client
station when sending data. The codes are as
follows: 0=Never, 1=Sometimes, 2=Always
DNPNET.CONFIG.DNP3_Ser
ver. Spare1_Always_1
Time period to wait for client Data Link
confirmation of last frame sent. This time is in
milliseconds. This parameter is only used if the
frame is sent with confirmation requested.
Commentaires sur ces manuels