MVI56E-DNPNET ♦ ControlLogix Platform Contents
DNPNET Ethernet Client/Server Communication Module User Manual
ProSoft Technology, Inc. Page 105 of 140
February 13, 2015
This field contains the hour value for the new time. Valid entry
for this field is in the range of 0 to 23.
This field contains the minute value for the new time. Valid
entry for this field is in the range of 0 to 59.
This field contains the second value for the new time. Valid
entry for this field is in the range of 0 to 59.
This field contains the millisecond value for the new time. Valid
entry for this field is in the range of 0 to 999.
Block 9998: Warm Boot
If the ControlLogix processor sends a block number 9998, the module performs a warm-
boot operation. The module will reconfigure the communication ports and reset the error and
status counters.
Block 9999: Cold Boot
If the ControlLogix processor sends a block number 9999, the module performs a cold-boot
operation. The firmware will reload the configuration file and reset all DNPNET memory,
error and status data.
4.3 MVI56E-DNPNET Database Overview
Output* Database
(PLC <- DNPNET)
Input* Database
(PLC -> DNPNET)
DNP OUTPUTS
(from remote
client to
DNPNET
Server)
DNP INPUTS
(from DNPNET
Server to
remote client)
A32OCount A32OPLC
(A32OIED)
A32ICount A32IPLC
(A32IIED)
FLTOCount FLTOPL
(FLTOIED)
FLTICount FLTIPLC
(FLTIIED)
DBLOCount DBLOPLC
(DBLOIED)
DBLICount DBLIPLC
(DBLIIED)
IED INPUTS
(from remote
server to
DNPNET Client)
IED OUTPUTS
(from DNPNET
Client to
remote server)
* Between DNPNET module and PLC, with respect to DNPNET module