MVI56E-DNPNET ♦ ControlLogix Platform Contents
DNPNET Ethernet Client/Server Communication Module User Manual
ProSoft Technology, Inc. Page 19 of 140
February 13, 2015
5 If you are using the module in a different slot (or remote rack), edit the connection input
and output variables that define the path to the module. Edit the text in the FINAL NAME
column (NAME column for controller revision 16 or less). For example, if your module is
located in slot 3, change Local:1:I in the above picture to Local:3:I. Do the same for
Local:1:O. If your module is located in Slot 1 of the local rack, this step is not required.
6 Click OK to confirm the import. RSLogix 5000 indicates that the import is in progress:
When the import is completed, the new rung with the Add-On Instruction will be visible
as shown in the following illustration.
The procedure also imports new User Defined Data Types, Controller Tags, and the
Add-On instruction for your project.
7 Save the application and then download the sample ladder logic into the processor.