Prosoft-technology MVI71-DFNT Manuel d'utilisateur Page 30

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 175
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 29
Installing and Configuring the Module MVI71-DFNT PLC 5
User Manual EtherNet/IP Client/Server Communication Module
Page 30 of 175 ProSoft Technology, Inc.
February 3, 2011
0 to 10000 milliseconds
ACK Timeout
This parameter specifies the number of milliseconds to wait for a DLE-ACK
character sequence after a response is issued.
2.2.4 [DFNT Client 0]
This section is used to define the configuration for the master device simulated
on network port
[DFNT Client 0]
Minimum Command Delay : 30 #Minimum number of msec’s between commands
Response Timeout : 1000 #Response message timeout (0-5000 mSec)
Retry Count : 3 #Response failure retry count
0 to 65535 milliseconds
Minimum Command Delay
This parameter specifies the number of milliseconds to wait between the initial
issuances of a command. This parameter can be used to delay all commands
sent to servers to avoid "flooding" commands on the network. This parameter
does not affect retries of a command as they will be issued when failure is
recognized.
0 to 65535 milliseconds
Response Timeout
This is the time in milliseconds that a Client will wait before re-transmitting a
command if no response is received from the addressed server. The value to use
depends on the type of communication network used, and the expected
response time of the slowest device on the network.
0 to 10
Retry Count
This parameter specifies the number of times a command will be retried if it fails.