Set the READ/WRITE parameter to WRITE. The module supports a TARGET DEVICE
parameter value of 500CPU
or PLC5. In order to complete the configuration of
the MSG instruction, select the S
ETUP SCREEN area of the MSG object. This
displays the following dialog box.
The T
ARGET DEVICE DATA TABLE ADDRESS must be set to a valid file element
(such as, N11:0) for SLC and PLC5 messages. The M
ULTIHOP option must be
set to Y
ES. The MULTIHOP tab portion of the dialog box must be completed as
displayed in the following window:
Set the IP address value to the module’s Ethernet IP address. You must press
the "Insert" key to add the second line for ControlLogix Backplane and set the
slot number to zero.