Prosoft-technology MVI69L-MBS Manuel d'utilisateur Page 93

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 154
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 92
MVI69L-MBS CompactLogix Platform Diagnostics and Troubleshooting
Communication Module User Manual
ProSoft Technology, Inc. Page 93 of 154
January 6, 2014
6.3.1 Setting Up a Temporary IP Address
Important: ProSoft Configuration Builder locates MVI69L-MBS modules through UDP broadcast
messages. These messages may be blocked by routers or layer 3 switches. In that case, ProSoft
Discovery Service is unable to locate the modules.
To use ProSoft Configuration Builder, arrange the Ethernet connection so that there is no router/
layer 3 switch between the computer and the module, OR reconfigure the router/ layer 3 switch to
allow routing of the UDP broadcast messages.
1 In the tree view in ProSoft Configuration Builder (PCB), select the MVI69L-
MBS module. (For instructions on opening and using a project in PCB, please
refer to Chapter 2.)
2 Click the right mouse button to open a shortcut menu. On the shortcut menu,
choose DIAGNOSTICS.
Vue de la page 92
1 2 ... 88 89 90 91 92 93 94 95 96 97 98 ... 153 154

Commentaires sur ces manuels

Pas de commentaire