Ladder Logic MVI69-HART ♦ CompactLogix Platform
User Manual HART Multi-drop Master Communication Module
Page 56 of 169 ProSoft Technology, Inc.
March 29, 2012
6 Select the Requested Packet Interval value for scanning the I/O on the
module. This value represents the minimum frequency at which the module
will handle scheduled events. It should not be set to less than 1 millisecond.
Values between 5 and 10 milliseconds should work with most applications.
7 S
AVE
the module. Click OK to dismiss the dialog box. The Controller
Organization window now displays the module's presence. The following
illustration shows the Controller Organization window:
8 Copy the User-defined Data Types (UDTs) from the sample program.
9 Copy the Controller Tags from the sample program.
10 Copy the Ladder Rungs from the sample program.
11 Save and download the new application to the controller.