Prosoft-technology MVI69-HART Manuel d'utilisateur Page 128

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 169
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 127
Reference MVI69-HART ♦ CompactLogix Platform
User Manual HART Multi-drop Master Communication Module
Page 128 of 169 ProSoft Technology, Inc.
March 29, 2012
5.8 HART Common Practice Commands
COMMAND 33 - Read Transmitter Variables
Description
This command gets four user selected dynamic Variables.
Write Parameters
Word High Byte Low Byte
0 Transmitter Variable Code For Slot 0 Transmitter Variable Code For Slot 1
1 Transmitter Variable Code For Slot 2 Transmitter Variable Code For Slot 3
Floating Point Data Returned
Word High Byte Low Byte
0 Variable for Slot 0
1
2 Variable for Slot 0
3
4 Variable for Slot 2
5
6 Variable for Slot 3
7
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
1 Transmitter Variable Code For Slot 0 Units Code for Slot 0 Variable
2 Transmitter Variable Code For Slot 1 Units Code for Slot 1 Variable
3 Transmitter Variable Code For Slot 2 Units Code for Slot 2 Variable
4 Transmitter Variable Code For Slot 3 Units Code for Slot 3 Variable
Vue de la page 127
1 2 ... 123 124 125 126 127 128 129 130 131 132 133 ... 168 169

Commentaires sur ces manuels

Pas de commentaire