Contents ILX69-PBS CompactLogix or MicroLogix Platform
User Manual PROFIBUS Slave Communication Module
Page 66 of 102 ProSoft Technology, Inc.
March 20, 2015
DPV1 Alarm
The DPV1 Class 1 Alarm Request is used to indicate a DPV1 Alarm to the master. The
MSG instruction Request/Response format is as follows.
ILX69PBS.CONTROL.DPV1.Alarm.Request
Parameter
Data Type
Value
Description
.Status
DINT
0x0000
Status of Alarm Request message
.Command
DINT
0x0221C
Command code
.SlaveAddress
SINT
Slave address
.AlarmType
SINT
Type of received alarm specified
.SlotNumber
SINT
0 to 255
Slot number module causing alarm
.Specifier
SINT
Alarm specifier
.Function
SINT
.Reserved
SINT
0
Reserved
ILX69PBS.CONTROL.DPV1.Alarm.Response
Parameter
Data Type
Value
Description
.Status
DINT
0x0000
Status of Alarm Request message, 0 = OK
.Command
DINT
0x0221C
Command code
.SlaveAddress
SINT
Slave address
.AlarmType
SINT
Type of received alarm specified
.SlotNumber
SINT
0 to 255
Slot number module causing alarm
.Specifier
SINT
Alarm specifier
.Function
SINT
.ErrorDecode
SINT
Error code
.ErrorCode1
SINT
Detailed error code
.ErrorCode2
SINT
User-specific error code