6.3.3 DPV1 Messaging
This section describes DPV1 messaging functions supported by the ILX69-PBS.
Note: Every DPV1 read or write request must be acknowledged by the
PLC application program. Otherwise, the PROFIBUS master shuts down
communication for both channels, V0 (cyclic IO data) and V1 (non-cyclic
messages). This can cause unexpected lost of data between the master
and the ILX69-PBS.
DPV1 Read
The DPV1 Class 1 Read Response message is used by the slave to reply to a Master DPV1
Read Request. The MSG instruction Response/Return format is as follows.
ILX69PBS.CONTROL.DPV1.Read.Response
Status of Response message
Slot number of data to be read
Index number of data to be read
Data length, 1 to 240 bytes
ILX69PBS.CONTROL.DPV1.Read.Return
Slot number of data to be read
Index number of data to be read