Modbus TCP/IP Protocol Configuration MNET ProLinx Gateway
Driver Manual Modbus TCP/IP Interface Module
Page 26 of 78 ProSoft Technology, Inc.
September 1, 2010
The first part of the record is the gateway Information, which relates to the
ProLinx gateway and the second part contains information required to interface
to the Server device.
Command list example:
2.5.4 Enable
YES, NO, or CONDITIONAL
This field defines whether the command is to be executed and under what
conditions.
Value Description
0 The command is disabled and will not be executed in the normal polling sequence.
1 The command is executed each scan of the command list if the Poll Interval Time is
set to zero. If the Poll Interval time is set, the command will be executed, when the
interval timer expires.
2 The command will execute only if the internal data associated with the command
changes. This value is valid only for write commands.