Reference DFNT ProLinx Gateway
Protocol Manual EtherNet/IP Explicit Messaging Client/Server
Page 110 of 124 ProSoft Technology, Inc.
July 24, 2013
Verify that the CIP radio-button is selected as the COMMUNICATION METHOD. The
PATH specifies the message route from the ControlLogix processor to the DFNT
module. Path elements are separated by commas. In the example path shown,
the first element is "Enet", which is the user-defined name given to the 1756-
ENET module in the chassis (you could substitute the slot number of the ENET
module for the name), the second element, "2", represents the Ethernet port on
the 1756-ENET module, and the last element of the path, "192.168.0.75", is the
IP address of the DFNT module, the target for the message.
More complex paths are possible if routing to other networks using multiple 1756-
ENET modules and racks. Refer to the Rockwell Automation Support
Knowledgebase for more information on Ethernet routing and path definitions.