Reference ProLinx-HART ♦ ProLinx Gateway
Driver Manual HART Master with Analog I/O
Page 50 of 104 ProSoft Technology, Inc.
October 13, 2011
COMMAND 15 - Read Output Information
Description
This command gets information about the Primary Variable Output Information.
Write Parameters
NONE
Floating Point Data Returned
Word High Byte Low Byte
0 Upper Range Value
1
2 Lower Range Value
3
4 Damping Value (Sec)
5
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
1 Alarm Select Code Transfer Function Code
2 Primary Variable Range Units Code Write-Protect Code
2 Private-Label Distributor Code 0