ProLinx-HART ♦ ProLinx Gateway HART Protocol Configuration
HART Master with Analog I/O Driver Manual
ProSoft Technology, Inc. Page 37 of 104
October 13, 2011
3.4 Using the CommonNet Data Map
The Data Map section allows you to copy data between areas in the module's internal
database.
You can copy a maximum of 100 registers per Data Map command, and you can
configure a maximum of 200 separate copy commands.
You can copy data from the error or status tables in upper memory to internal database
registers in the User Data memory area.
You can rearrange the byte and/or word order during the copy process. For example, by
rearranging byte or word order, you can convert floating-point values to the correct format
for a different protocol.
You can also use the Data Map to condense widely dispersed data into one contiguous
data block, making it easier to access.