MVI69-PDPMV1 CompactLogix or MicroLogix Platform Ladder Logic
PROFIBUS DPV1 Master User Manual
ProSoft Technology, Inc. Page 43 of 225
July 8, 2011
2.3 Adding the Module to an Existing MicroLogix Project
If you are installing and configuring the module with a MicroLogix controller,
follow these steps. If you are using a CompactLogix controller, refer to the
previous section.
The first step in setting up the processor ladder file is to define the I/O type
module to the system. Start RSLogix 500, and follow these steps:
1 In RSLogix, open your existing application, or start a new application,
depending on your requirements.
2 Double-click the
I/O CONFIGURATION icon located in the Controller folder in the
project tree. This action opens the
I/O Configuration dialog box.
3 In the
I/O Configuration dialog box, select "OTHER - REQUIRES I/O CARD TYPE
ID" at the bottom of the list in the right pane, and then double-click to open
the "Other" type IO card dialog box.
4 Enter the values shown in the following illustration to define the module
correctly for the MicroLogix processor, and then click OK
to save your
configuration.