MVI56E-MCMR ControlLogix Platform Start Here
Modbus Communication Module with Reduced Data Block User Manual
ProSoft Technology, Inc. Page 25 of 225
May 13, 2014
2 Select the 1756-MODULE (GENERIC 1756 MODULE) from the list and click OK.
This action opens the NEW MODULE dialog box.
3 Set the Module Properties values as follows:
Parameter
Value
Name
Enter a module identification string. The recommended value is
MCMR, as this name will be linked automatically with the MSG
paths, irrespective of the slot location.
Description
Enter a description for the module. Example: ProSoft
communication module for Modbus Serial protocol
communications.
Comm Format
Select DATA-INT (*Very Important*)
Slot
Enter the slot number in the rack where the MVI56E-MCMR
module is to be installed.
Input Assembly Instance
1
Input Size
42
Output Assembly Instance
2
Output Size
42
Configuration Assembly Instance
4
Configuration Size
0