5.2.3 PS69 LEDs
The LEDs as shown on the front panel will be used to indicate status information of the
PS69-DPM Master module. Each LED has a specific function during Run, configuration
download, and error indications. The following table shows the reaction of each during these
states for Master and Slave.
Device is in boot loader mode and is waiting for firmware
download.
Firmware download is in progress.
Hardware or runtime error detected.
Communication is running. The device has established at
least one configured fieldbus connection.
No error in configuration found, communication is stopped.
Power Up: Configuration missing or faulty, device needs
commissioning.
Runtime: Host Watchdog timeout
Device has no power supply or hardware defect.
Device is holding the PROFIBUS token and is able to transmit
telegrams.
Device is sharing the PROFIBUS token with other master
devices in the PROFIBUS network.
Device has found a communication problem to at least one
PROFIBUS-DP slave device or has detected a short circuit.
Device is not configured or has not received the Token
permission on the PROFIBUS network.
(*) 3 times fast at 5 Hz, 8 times between 0,5Hz and 1Hz
(**) between 0,5Hz and 100Hz