Prosoft-technology MVI46-MCM Manuel d'utilisateur Page 79

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 108
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 78
MVI46-MCM SLC Platform Reference
Modbus Communication Module User Manual
ProSoft Technology, Inc. Page 79 of 108
March 29, 2011
5.3.3 RS-422
The RS-422 interface requires a single four or five wire cable. The Common
connection is optional, depending on the RS-422 network devices used. The
cable required for this interface is shown below:
5.3.4 RS-485 Application Port(s)
The RS-485 interface requires a single two or three wire cable. The Common
connection is optional, depending on the RS-485 network devices used. The
cable required for this interface is shown below:
Note: Terminating resistors are generally not required on the RS-485 network, unless you are
experiencing communication problems that can be attributed to signal echoes or reflections. In
these cases, installing a 120-ohm terminating resistor between pins 1 and 8 on the module
connector end of the RS-485 line may improve communication quality.
RS-485 and RS-422 Tip
If communication in the RS-422 or RS-485 mode does not work at first, despite
all attempts, try switching termination polarities. Some manufacturers interpret +
and -, or A and B, polarities differently.
Vue de la page 78
1 2 ... 74 75 76 77 78 79 80 81 82 83 84 ... 107 108

Commentaires sur ces manuels

Pas de commentaire