Page 2 QTS-CLX-APACS March 2015
Each I/O connection supports:
scheduled input data, 496 SINTs or 124 REALs
scheduled output data, 496 SINTs or 124 REALs
The Windows configuration programs supplied with the module map IOBUS data to the
scheduled data. They also:
upload and download configuration data
map the IOBUS data to ControlLogix scheduled data
save and open configuration files
export aliases for use in your RSLogix 5000 application
change the module mode, between monitor and master modes
Firmware Update
The module firmware can be updated using the Change Module Mode functions in the
Windows utilities supplied (see page 44).
Part Number
The part number of the module is QTS-CLX-APACS.
Module Features
The following figure shows the features of the module.
The module has:
A label that identifies the module, text QTS
Universal Comm
A 4-character scrolling display
3 LEDs, labelled NET, CLX, and OK, to indicate
the status of the I/O bus, the state of the connection
to the ControlLogix processor, and the internal state
of the module
2 5-pin Phoenix connectors to connect to the IOBUS
A and IOBUS B bus cables
The module supports insertion and removal under power.
The module is shipped in monitor mode, with a blank configuration.