Vue de la page 54
Reference HART ProLinx Gateway
Driver Manual HART Master
ProSoft Technology, Inc. Page 55 of 119
July 7, 2009
COMMAND 06 - Write Polling Address
Description
This command sets the polling address of a HART device. Extreme care should
be taken when you use this command because you can loose the communication
with the device.
Write Parameters
Word High Byte Low Byte
0 Polling Address Polling Address
Floating Point Data Returned
NONE
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
1 Polling Address 0