Prosoft-technology MVI69E-MBTCP Manuel d'utilisateur Page 129

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 150
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 128
MVI69E-MBTCP CompactLogix Platform Reference
Modbus TCP/IP Enhanced Communication Module User Manual
ProSoft Technology, Inc. Page 129 of 150
May 20, 2015
7.4.2 Client Status Request/Response Blocks (3000 to 3019)
These blocks request the status of a specific MVI69E-MBTCP client.
Block 3000 or 3019: Request from Processor to Module
Offset
Description
0
Block ID 3000 to 3019 identification code indicates this block requests the
status from a specific MVI69E-MBTCP client. The last two digits indicate
which client to use.
Example: 3015 uses client 15
1 to (n-1)
Spare
Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.
Block 3000 to 3019: Response from Module to Processor
Offset
Description
0
Block ID 3000 to 3019 requested by the processor
1
Write Block ID
2 to 11
Client status data
12 to 27
Command error list data for client
28 to (n-1)
Spare
Vue de la page 128
1 2 ... 124 125 126 127 128 129 130 131 132 133 134 ... 149 150

Commentaires sur ces manuels

Pas de commentaire